آموزش بروز رسانی Frimware از طریق وب سرور برای پی ال سی S7-1200 S7-1500
5/5 - (1 امتیاز)

Training on updating Frimware or operating system for S7-1200 and S7-1500 PLC processors through web server

For PLC  S7-1200 processor version 3.0 and higher   and for  S7-1500 processor   with operating system version 1.1 and higher, firmware update can be done through the integrated web server. To update the firmware  , you must configure the processor in the Step 7  software  ( TIA Portal ) as follows:

agpl 01

Activate the processor web server

1. In the project navigation, right-click on the PLC folder   and select “Properties…” from the pop-up menu.

2. Click on the ” Web Server ” item in the navigation of the CPU properties area   and activate the “Activate web server on all modules of this device” option in the right window in the “General” section.

i5vp 03

1. Configure web server users (not required for S7-1200 PLC processors versions lower than 4.0)

1. Select “User management” in the Properties menu of the web server.

2. Enter username and password for user login to prepare

3. Open the access level setting through the drop-down menu.

 4. Select the access level “The user is allowed to update  the  firmware “.

5. Confirm the settings with “green tick” and close the dialog box with “OK”.

6. Save and compile the device configuration and   load your program into the CPU .

 

96yd 02

2. Update the firmware

  1. Unzip the firmware file into a directory on your hard drive.
  2. Open your Internet browser and enter the IP address of your processor in the address bar.
  3. If necessary, log in with the username and password selected in section 2.2.
  4. Open the “Module information” option in the menu.
  5. Select the name of the CPU station (here: “S7-1200 station_1”).
  6. Mark the processor slot.
  7. Open the “Firmware” tab.
  8. Using the “Browse…” button, navigate to the directory on your hard drive where you saved the update files. In the file “FWUPDATE.S7S” you need to select the file with the extension “.upd”.
  9. Click the “Run Update” button to start the update.
  10. Confirm the operation mode transition to “STOP” to perform the update.
  11. Do not leave the CPU web page during the update!

 12. A message will be displayed after  the firmware has been successfully loaded  into  the S7-1200 CPU  . Click  OK  to   put the processor  in  RUN mode.

 

Note: The images used in this tutorial are from STEP  7 software   ( TIA  Portal ) version 14.